Do SE8000 analog inputs accept a 4-20 mA signal?

Issue:
Need to connect a sensor with 4-20 mA output to SE8000 room controller.

Product Line: 
SE8000 room controllers 

Resolution:
  SE8000 room controllers do not accept a 4-20 mA signal, however, a 500 Ohm resistor across the input transforms 4-20 mA to 2-10 Vdc.
  