What are the Contact Resistance values for the Evolis 24KV Circuit Breaker.
The contact resistance values for the Evolis 24KV Circuit Breaker are tabulated below :   Evolis 24KV 16kA -630A 25kA-1250A 31.5kA-2500A Fixed Withdrawable...
Can an impulse-type power supply be used for electrical opening and closing order of Compact NS MCCB?
Yes, the impulse-type power supply (time duration > 20 ms and Voltage level above 0.7Un) can be used for electrical opening and closing of Compact...
What is the reference of Type A or Type B thermostat in Prisma Plus switchboard?
Type C thermostat is available in Prisma Plus, the part reference of which is 08998. The Type C thermostat Reference 08998 can be used as Type A or...
Is the Canalis range of products KBA, KBB, KDP halogen free.
Yes, the Canalis range of products KBA, KBB and KDP are halogen free. The Declaration of Conformity is attached.
What are the Contact Resistance values for the Evolis 17.5KV Circuit Breaker.
The contact resistance values for the Evolis 17.5KV Circuit Breaker are tabulated below:   Evolis 17.5KV Evolis 145mm Evolis 185mm Evolis 240mm Fixed...
What are the Contact Resistance values for the SF2 range MV Circuit Breaker.
The contact resistance values for the SF2 range MV Circuit Breaker are tabulated below :   SF2 SF2 Fixed SF2 in Mcset SF2 in F400 Contact Resistance...
Is the installation of 31097 locking kit same as the 31088 in Interpact source changeover system.
Yes, the installation of the 31097 & 31088 locking kits is the same, as all key locks have been designed to achieve locking in the OFF position. Refer...
What are the characteristics of SR13MAE (MAE500) trip unit used in Compact NS630 circuit breaker.
The Compact NS630 fitted with the STR13MAE trip unit is named: NS630MAE500.   The old MA500 trip unit was designed with mechanical feature. The new...
How to open an excel file during runtime in Vijeo Citect.
Below cicode function can be used during runtime for opening an Excel file in Vijeo Citect:   Exec("^""+"C:\Program Files\Microsoft Office\Office11\Excel.exe"+"^"...
How to redirect control clients to specific primary and Standby servers ?
By default client established connection either to primary or standby servers, However Control clients connection can be prioritized to connect either...