CONTROLEXPERT_V150_HF0367882E fixes the following issues (described below) • PEP0625393R Reference BOOL is reset when used on a Reset Coil that is not executed • IPR UNITY00102661: SIZEOF and EXTRACT Function Blocks behaves incorrectly in Program Unit section (P.U.) using Nested Derived Data Type referenced variable. • IPR UNITY00103076 - M580 6040: Unspecified behavior of RETURN instruction in ST language • Issue IPR UNITY00103087 BMEx584040 andBMEx586040: On PU Accessing arrays by reference in nested structures of Program Units And embeds Hot Fixes previously released: • ControlExpert_V150_HF_EPE_Evolution1 New behavior after installation of ControlExpert_V150_HF0367882E In above conditions the behavior is correct. What to do after installation of ControlExpert_V150_HF0367882E To repair the complete application a Full Expert Import application must be done. To repair the impacted section, modify a line adding a blank and Analyse or Build Changes