Why does my Magelis HMI show the error "PLC returned error code 10"?

Issue:
What does the following error message mean: "PLC returned error code 10"?

Product Line:
All Magelis programmed with Vijeo Designer

Resolution:
When communicating to a Micrologix PLC with your Magelis HMI you may see the error "PLC returned error code 10" when one or more of your HMI tags has an incorrect device address. To resolve this issue, please inspect your HMI variables and compare the device addresses you have configured against the PLC database.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
{"support":{"yesButton":"Yes","noButton":"No","feedback":{"title":"What can we do to improve?"},"submitButton":"Submit","successMessage":"Thank you for your feedback","title":"Did this answer your question?","feedbackPercentLabel":"of people found this helpful","captcha":{"error":"Please tick the box"}}}