intrinsically safe temperature input module Modicon Quantum - 8 I

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Modicon Quantum automation platform
    product or component type
    Intrinsically safe temperature input module
    software designation
    Concept version V2.2 and above
    Unity Pro
    type of filter
    Plus notch input filter 50/60 Hz thermocouple
    Single low pass input filter 20 Hz thermocouple
    Complementary
    product destination
    In conjunction with products for zone 20, 21 or 22
    analogue input number
    8
    analogue input type
    Low level voltage: -100...100 mV
    Low level voltage: -25...25 mV
    Thermocouple: - 210...760 °C for thermocouple J
    Thermocouple: - 270...1000 °C for thermocouple E
    Thermocouple: - 270...1370 °C for thermocouple K
    Thermocouple: - 270...400 °C for thermocouple T
    Thermocouple: - 50...1665 °C for thermocouple R
    Thermocouple: - 50...1665 °C for thermocouple S
    Temperature probe: - 200...850 °C for Pt 100, Pt 200, Pt 500, Pt 1000
    Temperature probe: - 60...180 °C for Ni 100, Ni 200, Ni 500, Ni 1000
    Thermocouple: - 130...1820 ° C for thermocouple B
    measurement current
    0.5 mA Pt 500, Pt 1000, Ni 500, Ni 1000
    2.5 mA Pt 100, Pt 200, Ni 100, Ni 200
    source resistance
    < 200 Ohm thermocouple
    input impedance
    > 10 MOhm RTD
    > 1 MOhm thermocouple
    common mode rejection
    > 100 dB 50/60 Hz RTD
    > 120 dB 50/60 Hz thermocouple
    cold junction compensation
    Internal 0…60 °C thermocouple
    linearity
    0.003 % of full scale RTD
    resolution
    0.76 µV (16 bits) -25...25 mV millivolt
    3.05 µV (16 bits) -100...100 mV millivolt
    1 °C, 0.1 °C, 1 °F, 0.1 °F thermocouple
    12 bits + sign (0.1 °C) RTD
    measurement accuracy
    +/- 2 °C + 0.1 % of reading thermocouple E
    +/- 2 °C + 0.1 % of reading thermocouple J
    +/- 2 °C + 0.1 % of reading thermocouple K
    +/- 2 °C + 0.1 % of reading thermocouple T
    +/- 4 °C + 0.1 % of reading thermocouple B
    +/- 4 °C + 0.1 % of reading thermocouple R
    +/- 4 °C + 0.1 % of reading thermocouple S
    +/- 0.5 °C RTD at 25 °C
    +/- 0.9 °C RTD at 0…60 °C
    20 µV + 0.1 % of reading millivolt at 25 °C
    absolute accuracy error
    +/- 0.05 % of full scale RTD at 25 °C
    +/- 0.1 % of full scale maximum RTD at 25 °C
    accuracy drift according to temperature
    0.15 mV/°C + 0.0015 % of reading/°C max thermocouple
    update time
    1 s TC/millivolt thermocouple
    1.35 s 3 wires RTD
    750 ms 2 or 4 wires RTD
    isolation between channels and bus
    1780 V 47...63 Hz AC for 1 minute
    2500 V DC for 1 minute
    fault type
    Broken wire
    Out of range
    power dissipation in W
    2 W
    hot swapping fallback
    Not allowed per intrinsic safety standards
    protection type
    Internal fuse
    marking
    CE
    II1 G/D-EEx ia IIC
    bus current requirement
    400 mA
    module format
    Standard
    product weight
    0.3 kg
    Environment
    standards
    EN 50281-1-1
    EN 50014
    EN 50284
    CSA C22.2 No 142
    EN 50020
    Directive ATEX 94/9/EC
    EN 50039
    dust zone
    Outside zone
    product certifications
    Hazardous location class 1, division 1 groups A, B, C
    C-Tick.1
    FM Class 1 Division 2
    SIRA 02ATEX2345X
    resistance to electrostatic discharge
    4 kV contact conforming to IEC 801-2
    8 kV on air conforming to IEC 801-2
    resistance to electromagnetic fields
    10 V/m 80…2000 Hz conforming to IEC 801-3
    ambient air temperature for operation
    0…60 °C
    ambient air temperature for storage
    -40…85 °C
    relative humidity
    95 % without condensation
    operating altitude
    <= 5000 m
    Contractual warranty
    Warranty
    18 months
  • Documents & Downloads

    Language
    • English
    User guide
    Date
    Size
    Add to My Documents
    Quantum using EcoStruxure™ Control Expert - Discrete and Analog I/O, Reference Manual (Version 16)
    Quantum with Concept and ProWORX, Hardware Reference Guide (Version 05)
    End of Life Information
    Date
    Size
    Add to My Documents
    Modicon Quantum automation platform, Product End-of-Life Instructions (Version 1.0)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
Nos conseillers sont disponibles pour répondre à vos questions de 8h00 à 18h00 du lundi au vendredi toute l'année.