What are the pinouts for the Output Relay on the Environmental Monitoring Unit (AP9319) and the Environmental Management System (AP9320)?


Below are the pinouts:


Pin #

Description

1

No Connection

2, 3

Normally Closed (NC) Contact

4, 5

Common

6, 7

Normally Open (NO) Contact (recommended connection)

8

No Connection


Relay ratings: 1A, 30V AC/DC