Issue
Unable to configure logical devices for EM4908E in ION Setup V3.2
Product
ION Setup
EM4908E
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop). *
A) Close ION Setup and find the location where ION Setup is installed, typically C:\Program Files (x86)\Schneider Electric\ION Setup\
B) Open the folder "Tables"
C) Open the folder "EM4900"
D) Open the folder "EM4908E"
E) Backup the file "Setup.cfg", save to a safe location
F) Edit the Setup.cfg with a text editor program such as notepad
G) Search for "[Logical Meter Setup]" (without quotes) there are 2 lines in this section to update
FlexCircuits=24
and
Registers=24
H) Save changes
I) Open ION Setup and configure the logical circuits for EM4908E meter
Note that a future version of ION Setup will have updated values.