Issue:
This document contains a video of how to change the Coil Fluid Temperature Thresholds on a Network Air FM Unit.
Product line:
FM 35-50, IR40, ACFM400, ACFM200.
Environment:
All Serial Numbers.
Cause:
Install, Configuration.
Resolution:
To change or set the coil fluid temperature threshold.
Press the ESC Key until you get to the main menu.
Press ENTER on Setup.
Press ENTER on System 1.
Press ENTER on Alarms.
Scroll down to Coil Fluid Thrshlds and press ENTER.
Using the UP or DOWN arrows you can select the High or Low threshold.
Press ENTER on either then change the value with the UP or DOWN arrow.
Finish by pressing the ENTER key and then press ESC until you get to the status menu.
This document contains a video of how to change the Coil Fluid Temperature Thresholds on a Network Air FM Unit.
Product line:
FM 35-50, IR40, ACFM400, ACFM200.
Environment:
All Serial Numbers.
Cause:
Install, Configuration.
Resolution:
To change or set the coil fluid temperature threshold.
Press the ESC Key until you get to the main menu.
Press ENTER on Setup.
Press ENTER on System 1.
Press ENTER on Alarms.
Scroll down to Coil Fluid Thrshlds and press ENTER.
Using the UP or DOWN arrows you can select the High or Low threshold.
Press ENTER on either then change the value with the UP or DOWN arrow.
Finish by pressing the ENTER key and then press ESC until you get to the status menu.
Publicado para: Schneider Electric Brasil




Precisa de ajuda?
Seletor de Produto
Encontre os produtos e acessórios certos para suas aplicações de forma rápida e fácil.
Obter um Orçamento
Inicie o seu pedido de contacto online e um especialista irá contactá-lo.
Onde comprar?
Encontre facilmente o distribuidor Schneider Electric mais próximo de suas instalações.
Centro de ajuda
Encontre recursos de apoio para todas as suas necessidades, num único local.