Issue:
Video: How to Configure network settings
Product line:
Symmetra PX 250-500
Environment:
All Product models, all serial numbers
Cause:
How do I Configure network settings on my Symmetra PX 250-500 UPS
Resolution:
Begin at the home screen of the UPS
Press the wrench key at the lower left of the screen
Select Configuration then User configuration
Enter the user password (apc by default)
Select NMC settings
Select Configure NMC Settings on the card you would like to configure.
Ensure the ‘UPS configuration access’ is set to read or read/write for the card
Make desired changes and Select Apply to save changes.
See the following video tutorial:
https://www.youtube.com/watch?v=_gfDhRQs6Z4&ab_channel=SchneiderElectric
Video: How to Configure network settings
Product line:
Symmetra PX 250-500
Environment:
All Product models, all serial numbers
Cause:
How do I Configure network settings on my Symmetra PX 250-500 UPS
Resolution:
Begin at the home screen of the UPS
Press the wrench key at the lower left of the screen
Select Configuration then User configuration
Enter the user password (apc by default)
Select NMC settings
Select Configure NMC Settings on the card you would like to configure.
Ensure the ‘UPS configuration access’ is set to read or read/write for the card
Make desired changes and Select Apply to save changes.
See the following video tutorial:
Publicado para:Schneider Electric Brasil



