What is the recommended supply transformer for the 120Vac shunt trip for EDB, EGB, and EJB breakers?

Published date: 24 April 2019

Product Line:
Circuit Breakers
EDB, EGB, EJB

Environment:
Electrical Distribution Equipment

Resolution:
Minimum Control Power Transformer (CPT) = 50 VA
Coil Burden Max. = 288 VA Voltage = 120 Vac 50/60 Hz
 