Canada
Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Select your location
View all Altivar 61
Schneider Eletric

ATV61HC11Y

Green premium brand logo
Schneider Eletric
ATV61HC11Y
Green premium brand logo

variable speed drive ATV61 - 110kW / 690V - 125HP / 575V - IP20

Show more characteristics
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Altivar 61
    product or component type
    Variable speed drive
    product specific application
    Pumping and ventilation machine
    component name
    ATV61
    motor power kW
    110 kW, 3 phases 690 V
    90 kW, 3 phases 500 V
    motor power hp
    125 hp, 3 phases 575 V
    power supply voltage
    500...690 V - 15...10 %
    supply number of phases
    3 phases
    line current
    113 A 600 V 3 phases 90 kW / 125 hp
    117 A 690 V 3 phases 90 kW / 125 hp
    128 A 500 V 3 phases 90 kW / 125 hp
    EMC filter
    Level 3 EMC filter
    assembly style
    With heat sink
    maximum prospective line Isc
    22 kA 3 phases
    maximum transient current
    163.2 A 60 s, 3 phases
    nominal switching frequency
    2.5 kHz
    switching frequency
    2.5...4.9 kHz adjustable
    2.5...4.9 kHz with derating factor
    asynchronous motor control
    Flux vector control without sensor, standard
    Voltage/frequency ratio - Energy Saving, quadratic U/f
    Voltage/frequency ratio, 2 points
    Voltage/frequency ratio, 5 points
    synchronous motor control profile
    Vector control without sensor, standard
    communication port protocol
    CANopen
    Modbus
    type of polarization
    No impedance Modbus
    option card
    Communication card APOGEE FLN
    Communication card BACnet
    Communication card CC-Link
    Controller inside programmable card
    Communication card DeviceNet
    Communication card Ethernet/IP
    Communication card Fipio
    I/O extension card
    Communication card Interbus-S
    Communication card LonWorks
    Communication card METASYS N2
    Communication card Modbus Plus
    Communication card Modbus TCP
    Communication card Modbus/Uni-Telway
    Multi-pump card
    Communication card Profibus DP
    Communication card Profibus DP V1
    Complementary
    product destination
    Asynchronous motors
    Synchronous motors
    power supply voltage limits
    425…759 V
    power supply frequency
    50...60 Hz - 5...5 %
    power supply frequency limits
    47.5...63 Hz
    continuous output current
    125 A 2.5 kHz, 575 V - 3 phases
    125 A 2.5 kHz, 690 V - 3 phases
    136 A 2.5 kHz, 500 V - 3 phases
    output frequency
    0.1…500 Hz
    speed range
    1…100 in open-loop mode, without speed feedback
    speed accuracy
    +/- 10 % of nominal slip 0.2 Tn to Tn without speed feedback
    torque accuracy
    +/- 15 % in open-loop mode, without speed feedback
    transient overtorque
    130 % of nominal motor torque +/- 10 % 60 s
    braking torque
    <= 125 % with braking resistor
    30 % without braking resistor
    regulation loop
    Frequency PI regulator
    motor slip compensation
    Can be suppressed
    Automatic whatever the load
    Not available in voltage/frequency ratio (2 or 5 points)
    Adjustable
    diagnostic
    Drive voltage 1 LED red)
    output voltage
    <= power supply voltage
    electrical isolation
    Between power and control terminals
    type of cable for mounting in an enclosure
    With an IP21 or an IP31 kit 3 IEC cable 104 °F (40 °C), copper 70 °C / PVC
    With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC
    Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC
    Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR
    electrical connection
    Terminal 2.5 mm² / AWG 14 AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)
    Terminal 2 x 120 mm² / 2 x 250 kcmil L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
    Terminal 120 mm² / 250 kcmil PA, PB)
    Terminal 2 x 120 mm² / 2 x 250 kcmil PC/-, PA/+)
    tightening torque
    5.31 lbf.in (0.6 N.m) AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)
    212.42 lbf.in (24 N.m), 212 lb.in L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
    212.42 lbf.in (24 N.m), 212 lb.in PA, PB)
    212.42 lbf.in (24 N.m), 212 lb.in PC/-, PA/+)
    supply
    Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC, +/- 5 %, <10 mA overload and short-circuit protection
    Internal supply 24 V DC 21…27 V), <200 mA overload and short-circuit protection
    External supply 24 V DC 19…30 V)
    analogue input number
    2
    analogue input type
    AI1-/Al1+ bipolar differential voltage +/- 10 V DC 24 V max 11 bits + sign
    AI2 software-configurable current 0...20 mA 242 Ohm 11 bits
    AI2 software-configurable voltage 0...10 V DC 24 V max 30000 Ohm 11 bits
    sampling time
    2 ms +/- 0.5 ms AI1-/Al1+) - analog input
    2 ms +/- 0.5 ms Al2) - analog input
    2 ms +/- 0.5 ms AO1) - analog output
    2 ms +/- 0.5 ms LI1...LI5) - discrete input
    2 ms +/- 0.5 ms LI6)if configured as logic input - discrete input
    absolute accuracy precision
    +/- 0.6 % AI1-/Al1+) for a temperature variation 60 °C
    +/- 0.6 % AI2) for a temperature variation 60 °C
    +/- 1 % AO1) for a temperature variation 60 °C
    linearity error
    +/- 0.15 % of maximum value AI1-/Al1+)
    +/- 0.15 % of maximum value AI2)
    +/- 0.2 % AO1)
    analogue output number
    1
    analogue output type
    AO1 software-configurable current 0...20 mA 500 Ohm 10 bits
    AO1 software-configurable voltage 0...10 V DC 470 Ohm 10 bits
    AO1 software-configurable logic output 10 V, 20 mA
    discrete output number
    2
    discrete output type
    Configurable relay logic R1A, R1B, R1C) NO/NC - 100000 cycles
    Configurable relay logic R2A, R2B) NO - 100000 cycles
    maximum response time
    <= 100 ms in STO (Safe Torque Off)
    R1A, R1B, R1C <= 7 ms +/- 0.5 ms
    R2A, R2B <= 7 ms +/- 0.5 ms
    minimum switching current
    3 mA 24 V DC configurable relay logic
    maximum switching current
    R1, R2 2 A 250 V AC inductive, cos phi = 0.4 7 ms
    R1, R2 2 A 30 V DC inductive, cos phi = 0.4 7 ms
    R1, R2 5 A 250 V AC resistive, cos phi = 1 0 ms
    R1, R2 5 A 30 V DC resistive, cos phi = 1 0 ms
    discrete input number
    7
    discrete input type
    Programmable LI1...LI5) 24 V DC <= 30 V)level 1 PLC - 3500 Ohm
    Switch-configurable LI6) 24 V DC <= 30 V)level 1 PLC - 3500 Ohm
    Switch-configurable PTC probe LI6)0…6 - 1500 Ohm
    Safety input PWR) 24 V DC <= 30 V) - 1500 Ohm
    discrete input logic
    Negative logic (sink) LI1...LI5), > 16 V, < 10 V
    Positive logic (source) LI1...LI5), < 5 V, > 11 V
    Negative logic (sink) LI6)if configured as logic input, > 16 V, < 10 V
    Positive logic (source) LI6)if configured as logic input, < 5 V, > 11 V
    acceleration and deceleration ramps
    Automatic adaptation of ramp if braking capacity exceeded, by using resistor
    Linear adjustable separately from 0.01 to 9000 s
    S, U or customized
    braking to standstill
    By DC injection
    protection type
    Against exceeding limit speed drive
    Against input phase loss drive
    Break on the control circuit drive
    Input phase breaks drive
    Line supply overvoltage drive
    Line supply undervoltage drive
    Overcurrent between output phases and earth drive
    Overheating protection drive
    Overvoltages on the DC bus drive
    Power removal drive
    Short-circuit between motor phases drive
    Thermal protection drive
    Motor phase break motor
    Power removal motor
    Thermal protection motor
    insulation resistance
    > 1 mOhm 500 V DC for 1 minute to earth
    frequency resolution
    Analog input 0.024/50 Hz
    Display unit 0.1 Hz
    connector type
    1 RJ45 on front face)Modbus
    1 RJ45 on terminal)Modbus
    Male SUB-D 9 on RJ45CANopen
    physical interface
    2-wire RS 485 Modbus
    transmission frame
    RTU Modbus
    transmission rate
    4800 bps, 9600 bps, 19200 bps, 38.4 Kbps Modbus on terminal
    9600 bps, 19200 bps Modbus on front face
    20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps CANopen
    data format
    8 bits, 1 stop, even parity Modbus on front face
    8 bits, odd even or no configurable parity Modbus on terminal
    number of addresses
    1…127 CANopen
    1…247 Modbus
    method of access
    Slave CANopen
    marking
    CE
    operating position
    Vertical +/- 10 degree
    net weight
    224.87 lb(US) (102 kg)
    width
    13.39 in (340 mm)
    height
    46.85 in (1190 mm)
    depth
    14.84 in (377 mm)
    Environment
    noise level
    77 dB 86/188/EEC
    dielectric strength
    3110 V DC between earth and power terminals
    5345 V DC between control and power terminals
    electromagnetic compatibility
    Conducted radio-frequency immunity test level 3 IEC 61000-4-6
    Electrical fast transient/burst immunity test level 4 IEC 61000-4-4
    Electrostatic discharge immunity test level 3 IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
    Voltage dips and interruptions immunity test IEC 61000-4-11
    standards
    EN 55011 class A group 2
    EN 61800-3 environments 2 category C3
    EN 61800-3 environments 1 category C3
    EN/IEC 61800-5-1
    UL Type 1
    EN/IEC 61800-3
    IEC 60721-3-3 class 3C2
    product certifications
    NOM 117
    CSA
    DNV
    C-Tick
    GOST
    UL
    pollution degree
    3 EN/IEC 61800-5-1
    3 UL 840
    degree of proctection
    IP41 on upper part EN/IEC 60529
    IP41 on upper part EN/IEC 61800-5-1
    IP54 on lower part EN/IEC 60529
    IP54 on lower part EN/IEC 61800-5-1
    IP00 EN/IEC 60529
    IP00 EN/IEC 61800-5-1
    IP30 on side parts EN/IEC 60529
    IP30 on side parts EN/IEC 61800-5-1
    IP30 on the front panel EN/IEC 60529
    IP30 on the front panel EN/IEC 61800-5-1
    vibration resistance
    0.6 gn 10…200 Hz)EN/IEC 60068-2-6
    1.5 mm peak to peak 3…10 Hz)EN/IEC 60068-2-6
    shock resistance
    7 gn 11 ms EN/IEC 60068-2-27
    relative humidity
    5…95 % without condensation IEC 60068-2-3
    5…95 % without dripping water IEC 60068-2-3
    ambient air temperature for operation
    14…113 °F (-10…45 °C) without)
    113…140 °F (45…60 °C) with derating factor)
    ambient air temperature for storage
    -13…158 °F (-25…70 °C)
    operating altitude
    <= 1000 m without
    1000...2260 m with current derating 1 % per 100 m
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    REACh Regulation
    EU RoHS Directive
    Not applicable, out of EU RoHS legal scope
    Mercury free
    Yes
    RoHS exemption information
    China RoHS Regulation
    Environmental Disclosure
    Circularity Profile
    No need of specific recycling operations
    End of Life Information
    WEEE
    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
    Contractual warranty
    Warranty
    18 months
  • Documents

    Language
    • English
    • French
    Catalogue
    Date
    Size
    Add to My Documents
    Catalog: Altivar 61/61 Plus variable speed drives - English version 2014/04 (web pdf format) (Version 1.0)
    User guide
    Date
    Size
    Add to My Documents
    ATV61 Programming manual (Version 09)
    Date 26/02/14
    Size 4.4 MB
    ATV61 Guide de programmation (Version 09)
    Date 26/02/14
    Size 8.1 MB
    ATV61 Quick Start annex: SCCR and branch circuit protection (Version 03)
    2) ATV61 Guide d'installation 55-800 kW (Version 05)
    ATV61_GUIDE INSTALLATION_ (75-125HP_240V)(125-900HP_480V) (125-800HP_600V)_FR (Version 1)
    ATV61-71 to ATV600-900 Migration Manual (Version 01)
    ATV61/71/ LIFT Safety integrated function manual (Version 04)
    CAD
    Date
    Size
    Add to My Documents
    CAD for ATV61HC11Y: variable speed drive ATV61 - 110kW / 690V - 125HP / 575V - IP20 (Version 1.0)
    Certificate
    Date
    Size
    Add to My Documents
    ATV61 EU DECLARATION (Version 1.0)
    Date 20/04/16
    Size 2.1 MB
    Catalogue Page
    Date
    Size
    Add to My Documents
    Altivar 61 - Option : AFE (Version 1.2)
    Date 09/09/10
    Size 170.2 KB
    End of Life Information
    Date
    Size
    Add to My Documents
    ALTIVAR 61, 90 - 800 kW - ALTIVAR 71, 90 - 630 kW, Product End-of-Life Instructions (Version 2.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 23/10/19
    Size 195.3 KB
    Marine certificate
    Date
    Size
    Add to My Documents
    ATV61-71_RINA_CERTIFICATE (Version 1.0)
    Date 08/02/18
    Size 2.6 MB
    LR Marine Certificate ATV61 Altivar VSD (Version 1.0)
    DNV-GL Marine Certificate ATV61 variable speed drives (Version 1.0)
    BV Marine Certificate ATV61 <50KW variable speed drives (Version 1.0)
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    Altivar 61 De 90 à 800 kW, PEP (Version 1.0)
    Date 01/12/09
    Size 883.5 KB
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 23/10/19
    Size 195.3 KB
    RoHs China Declaration
    Date
    Size
    Add to My Documents
    Date 23/10/19
    Size 195.3 KB
  • Software and Firmware

    Language
    • English
    • Spanish
    • Portuguese
    • French
    • Italian
    • German
    • Chinese
    • Turkish
    Software - Released
    Date
    Size
    Add to My Documents
    SoMove V2.7.6 (FDT Standalone) (Version 2.7.6)
    Date 23/09/19
    Size 280.6 MB
    Date 23/09/19
    Size 134.3 KB
    DTM files
    Date
    Size
    Add to My Documents
    Altivar DTM Library V12.8: ATV12, ATV31/312, ATV32, ATV61, ATV71, ATV LIFT, ATV212 (Version 12.8)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.