{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Jak vám dnes můžeme pomoci?
User name and password lengths for InfraStruXure Central and Netbotz appliances for an SNMP version 3 inform.
Issue:

User name and password lengths for InfraStruXure Central and Netbotz appliances for an SNMP version 3 inform.

Product Line:

NetBotz
InfraStruxure Central

Environment:

Netbotz SNMP v3

Cause:

SNMP version 3 requirements

Resolution:

v3 informs only work under certain circumstances.

md5/des user/password must be 8-15 characters
md5/aes user/password must be 8-15 characters
sh1/aes user/password must be 16+ characters
sh1/des user/password must be 16+ characters

for md5 the user name and password only work if they are between 8-15 characters.
for sh1 the user name and password only work if they are >16 characters.

Schneider Electric Česká republika

Zjistěte více
Řada:
Užitečné články
Zjistěte více
Řada: