{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Prohledejte časté dotazy
What is the max duty cycle for the ATS01 soft starters?
Issue:
ATS01 duty cycle.
Product Line:
Altistart 01
ATS01
Environment:
Frequent start/stop cycles
Cause:
Overheating
Resolution:

There are several different versions of ATS01.  Each has it's own characteristics.
See below:

ATS01N1...FT
1 second start time, 100 maximum number of starts per hour
5 second start time, 20 maximum number of starts per hour

ATS01N2206 to N222, LU, QN, RT
1 second start time, 100 maximum number of starts per hour
5 second start time, 20 maximum number of starts per hour
10 second start time, 10 maximum number of starts per hour

ATS01N232, LU, QN, RT
1 second start time, 50 maximum number of starts per hour
5 second start time, 10 maximum number of starts per hour
10 second start time, 5 maximum number of starts per hour

ATS01N2... LY, Q THIS VERSION IS NO LONGER AVAILABLE see the ATS22 product family instead
1 second start time, 360 maximum number of starts per hour
12 second start time, 30 maximum number of starts per hour

Schneider Electric Česká republika

Přílohy
ATS01 cycle Times.pdf [22.28 KB]
Zjistěte více
Řada:
Užitečné články
Zjistěte více
Řada: