Wie können wir Ihnen heute helfen?

Web Reporter fails to install report packs: "Object reference not set to an instance of an object".

Issue:

When installing default report packs with either the command line utility or configuration wizard, installation fails and shows:

System.NullReferenceException: Object reference not set to an instance of an object
and references a pack such as:
C:\Program Files\Schneider Electric\ION Enterprise\Web\ReportPacks\Default Reports 6.0.zip

Product Line:

PME 8.0

Environment:

Legacy Web Reporter
ION_Network database

Cause:

The ION_Network database schema version does not match the installed software (for example, a 6.0 database copied into a 6.0 SP1 system without being upgraded). In this condition, Web Reporter cannot find required assets during pack installation and throws a NullReferenceException.

Warning: Irreparable database damage can occur. Only users familiar with SQL Server Management Studio should perform this procedure.

Resolution:

  1. Verify the database version
    Open ION_Network.dbo.Registry and check the Revision value. If it does not correspond to the installed product level, the database must be upgraded.
  2. Upgrade ION_Network
    Use Database Manager from the Management Console to upgrade ION_Network to the correct version. Confirm completion without errors.
  3. Ensure services are ready
    Confirm SQL Server Agent is running and the application services for reporting are started.
  4. Re‑install report packs
    Run the configuration wizard again. The installation should complete successfully with the corrected schema.

Recommendation:

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

PME Version History

Schneider Electric Deutschland

Weitere Produktinformationen
Bereich:
Weitere Produktinformationen
Bereich:
  • Produktdokumentation
  • Software-Downloads
  • Produktauswahlhilfe
  • Produktersatz und -austausch
  • Hilfe- und Kontaktzentrum
  • Niederlassungen finden
  • Schließung von shop.se.com/de/de
  • Schneider Electric Community
  • Karriere
  • Unternehmensprofil
  • Fehlverhalten melden
  • Accessibility
  • Newsroom
  • Investoren
  • EcoStruxure
  • Job suchen
  • Blog
  • Impressum
  • Datenschutzerklärung
  • Cookie-Hinweis
  • Nutzungsbedingungen
  • AGB
  • Cookie-Einstellungen