{}

Unsere Marken

Impact-Company-Logo-English Black-01-177x54

Willkommen auf der Website von Schneider Electric

Willkommen auf unserer Website.
Wie können wir Ihnen heute helfen?
On the ATV630 and ATV930 process drives, why can't the digital input assignments be changed?
Issue:
ATV630/ATV930 the digital input assignments are not changing in the Input/Output menu?

Product Line:
Altivar Process, Altivar 630, ATV630, Altivar 930, ATV930

Environment:
All models

Cause:
Attempting to change DIx assignments in the COMPLETE SETTINGS > INPUT/OUTPUT menu

Resolution:
The digital input assignments in the INPUT/OUTPUT menu are read only.  To change an assignment, you need to go to the desired function and then assign an Input to the function. Example: to assign Reverse to DI2, you need to go to "Reverse assign" in the Command and Reference menu, and change that to DI2.

Link to the ATV600 programming manual:  https://download.schneider-electric.com/files?p_Doc_Ref=EAV64318
Link to the ATV900 programming manual;  https://www.se.com/us/en/download/document/NHA80757/

Schneider Electric Deutschland

Weitere Produktinformationen
Bereich:
Artikel, die hilfreich sein könnten
Weitere Produktinformationen
Bereich: