{}

Unsere Marken

Impact-Company-Logo-English Black-01-177x54

Willkommen auf der Website von Schneider Electric

Willkommen auf unserer Website.
Wie können wir Ihnen heute helfen?
Video: How to Shutdown your Silcon UPS
Issue:
How to Shutdown your Silcon UPS

Product line:
Silcon DP300E

Environment:
All Product models, all serial numbers

Cause:
Shutdown Support

Resolution:
First step is to put the UPS into bypass



Hit the # Key and then Press "C" to change the option to yes



Press the # key again to save change.
The UPS is now in static bypass.

H3 LED will light indicating it is safe to operate Q3
Turn the Q3 switch on



H2 LED will light indicating it is safe to operate Q2
Turn the Q2 switch Off



Open the front door of the UPS and Press the Red button (acoustic alarm will sound for 30 seconds)
Open all battery breakers (or fuses)
Turn off the Q1 switch
Your UPS is now off

The following video demonstrates this procedure:

Schneider Electric Deutschland

Weitere Produktinformationen
Bereich:
Artikel, die hilfreich sein könnten
Weitere Produktinformationen
Bereich: