Issue:
Request for the short circuit ratings of the SYBTU1, and SYBTU2 batteries.
Product line:
Symmetra PX, Smart UPS VT
Environment:
All models, all serial numbers
Cause:
Request for information on the short circuit ratings of the battery modules used in the Symmetra PX and Smart UPS VT systems.
Resolution:
The short circuit rating of the battery module is limited by the fuses inside it. The SYBTU1-PLP, and SYBTU2-PLP battery modules have fuse part #515-1063-Z.
Fuse Fast 63 Amp 500 VDC / 690 VAC ROHS
Bussmann Spec Sheet attached.
Request for the short circuit ratings of the SYBTU1, and SYBTU2 batteries.
Product line:
Symmetra PX, Smart UPS VT
Environment:
All models, all serial numbers
Cause:
Request for information on the short circuit ratings of the battery modules used in the Symmetra PX and Smart UPS VT systems.
Resolution:
The short circuit rating of the battery module is limited by the fuses inside it. The SYBTU1-PLP, and SYBTU2-PLP battery modules have fuse part #515-1063-Z.
Fuse Fast 63 Amp 500 VDC / 690 VAC ROHS
Bussmann Spec Sheet attached.