{}

Vores varemærker

Impact-Company-Logo-English Black-01-177x54

Velkommen til Schneider Electrics website

Velkommen til vores website
Hvordan kan vi hjælpe dig i dag?
Video: How to reset an Air Filter Run Hours violation alarm on a Uniflair Unit
Issue:
This video shows how to reset an Air Filter Run Hours violation alarm on a Uniflair Unit.

Product line:
All Unfair Units with Push-Button Display, All Chilled Water Uniflairs.

Environment:
All Serial Number with Push-Button Units.

Cause:
Repair, Install, Maintenance.

Resolution

To clear Air filters run  hour violations from a Uniflair push button display.

Press <> PRG.

Settings Menu <> ENTER.

Code <> 00000 ENTER.

Hour-Meter Settings <> ENTER.

ENTER down to reset hit ENTER change display to OK and then ENTER Again.

Alarm has been cleared. Review the following video for a demonstration of this procedure.

Schneider Electric Danmark

Se mere
Område:
Artikler som kan være nyttige
Se mere
Område: