Issue:
InRow Entering Fluid Temp threshold is not alarming
Product line:
InRow
Environment:
Data Center Cooling
Cause:
Resolution:
In the newest firmware ACRC 372 and higher the entering fluid temp alarm threshold violation will not be reported unless two conditions are met. The unit has a >=40% valve position opening, and the entering temperature is above the threshold.