ISX-PDU Load High threshold alarm

Article available in these languages: Espagnol


Title:
ISX-PDU Load High threshold alarm

Issue:
ISX-PDU goes into alarm state when load crosses High threshold alarm setting.

Product line:
ISX-PDU120V


Environment:
All models, all serial numbers

Cause:
Load on phase has crossed threshold set by customer.

Resolution:
Balance load or raise threshold alarm setting

Use the display interface to configure settings, set alarm thresholds, and provide audible and visual alarms.