Why is there a Pack 0 showing on the PowerView display of my SURT 15/20kVA UPS?
Issue
The PowerView display of SURT 15/20kVA UPS shows the status of a Pack 0 in the Batteries menu.

Product Line
Smart-UPS 15/20kVA

Environment
  • Smart-UPS 15/20kVA All Models
  • SURT192RMXLBP2

Cause
Pack 0 represents the global battery status if the system is using non-APC batteries in the UX configuration.
In a non-UX configuration, the Pack 0 status screen will still be available on the PowerView display even if the system has only APC battery packs connected. However, Pack 01 represents the 1st APC battery cabinet connected to the UPS, Pack 02 the 2nd APC battery cabinet, and so on.

Resolution
If using APC batteries, the values reported for Pack 0 can be ignored.

Schneider Electric Algeria

Besoin d'aide ?

  • Sélecteur de produits

    Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.

  • Obtenir un devis

    Effectuez une demande de renseignements en ligne et un expert vous contactera.

  • Où acheter ?

    Trouvez facilement le distributeur Schneider Electric local le plus proche.

  • Centre d'aide

    Trouvez des ressources de support pour tous vos besoins, en un seul endroit.

  • Documentation produit
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Politique de confidentialité
  • Mention sur les cookies
  • Change your cookie settings