Welcome to the Schneider Electric Website

Welcome to our website.

Select your location

Welcome the the Schneider Electric French website. It looks like you are located in the United States, would you like to change your location?

Traduisez en francais
View all   Modicon X80 I/Os
BMXCPS4002 Product picture Schneider Electric

BMXCPS4002

Green premium brand logo
BMXCPS4002 Product picture Schneider Electric
BMXCPS4002
Green premium brand logo

power supply module X80 - 100..240 V AC

Show more characteristics
The maximum number of products that can be compared is 4. Remove already added products.

  • Main
    range of product
    Modicon X80
    product or component type
    Power supply module
    backplane compatibility
    All backplane
    advanced diagnostics available via network
    Temperature sensing
    Redundancy test
    Uptime duration
    Redundancy information
    Remaining lifetime
    primary voltage
    100...240 V
    supply circuit type
    AC
    secondary power
    18 W 3.3 V DC at 0…60 °C I/O module logic power supply
    40 W 24 V DC at 0…60 °C I/O module power supply and processor if 3.3 V not loaded
    Complementary
    primary voltage limit
    85...264 V
    network frequency
    50/60 Hz
    network frequency limits
    47…63 Hz
    apparent power
    0.07 kVA
    input current
    0.52 A 240 V
    1.04 A 115 V
    inrush current
    30 A 120 V
    60 A 240 V
    I²t on activation
    1 A².s 115 V
    4 A².s 230 V
    It on activation
    0.1 A.s 115 V
    0.15 A.s 230 V
    protection type
    Internal fuse not accessible for primary circuit
    Overload protection for secondary circuit
    Overvoltage protection for secondary circuit
    Short-circuit protection for secondary circuit
    current at secondary voltage
    5.5 A 3.3 V DC I/O module logic power supply
    1.67 A 24 V DC I/O module power supply and processor
    maximum power dissipation in W
    8.5 W
    status LED
    1 LED (green)presence of voltages (OK)
    1 LED (green)redundancy OK
    1 LED (green)power supply status
    control type
    RESET push-button cold restart
    electrical connection
    1 connector 2 pin(s)alarm relay
    1 connector 5 pin(s)line supply, protective earth
    insulation resistance
    >= 100 MOhm primary/ground
    >= 100 MOhm primary/secondary
    net weight
    0.51 kg
    Environment
    immunity to microbreaks
    1 ms
    dielectric strength
    1500 V primary/secondary I/O module logic power supply
    1500 V primary/secondary I/O module power supply and processor
    2300 V primary/secondary sensor power supply
    1500 V primary/ground
    500 V 24 V sensor output/ground
    vibration resistance
    3 gn
    shock resistance
    30 gn
    IP degree of protection
    IP20