{}

Nuestras marcas

Impact-Company-Logo-English Black-01-177x54

Web de Schneider Electric España

Bienvenido a nuestra web
Preguntas frecuentes de búsqueda
Data Center Expert | How do I upgrade my software version?
Issue:
Process for upgrading StruxureWare Data Center Expert.

Product Line
StruxureWare Data Center Expert (DCE)
- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)

Environment:
StruxureWare Data Center Expert (all versions)

Resolution:

You must have a valid currently active software support contract to receive upgrade files.

See FA372574 for instructions on preparing for the upgrade, which include:
  • Software Support verification through technical support to receive upgrade files.
  • Verifying the Checksum (integrity) of upgrade files.
  • Virtual Appliance hard disk requirements.
  • Creating a Backup before upgrading.



1) Download the upgrade.zip file and verify the checksum.

2) Extract the downloaded upgrade.zip file. As of 7.9.3 going forward, extracting the contents of the zip file is not required.

3) Login to the DCE Desktop Client, select the Updates Menu, and then select Apply Server Update.

4) Select Import and navigate to the extracted upgrade file. (or zip file if 7.9.3 or higher.)  Select Open.

5) Select Install Update to start upgrading the server.

6) Monitor the progress of the update on the web interface of DCE.
NOTE: Upgrades usually take an hour or less to complete, but for certain upgrades it may take significantly longer depending on the number of devices and amount of historical data.

7) When prompted for login on the web interface, log in and install the new desktop client.  Instructions for downloading and installing the desktop client can be found in knowledge base FA272226.

Schneider Electric España

Explorar más
Producto:
Artículos que pueden ser útiles
Explorar más
Producto: