Issue:
ATV212 or ATV21 set up to start/stop on terminal and ramp to 60 Hz
Product Line:
ATV21, ATV212
Environment:
All models and serial numbers.
Cause:
None
Resolution:
Begin by wiring the remote start switch or relay for two wire control between terminals P24 and F.
Program the nameplate motor parameters into the following parameters:
CODE - DESCRIPTION |
thr - Motor thermal prot. |
uLu - Motor rated voltage |
F415 - Motor rated current |
F417 - Motor rated speed |
Make the following parameter settings:
CODE - DESCRIPTION | SETTING |
LL - Low limit frequency | as desired |
UL - Upper limit freq | 60 |
Dec - Deceleration ramp time | as desired |
ACC - Acceleration ramp time | as desired |
CMOD - Command mode selection | 0 |
“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Publicado para: Schneider Electric España


¿Necesitas ayuda?
Empieza aquí
Encuentra respuestas ahora. Busca una solución por ti mismo, o ponte en contacto con uno de nuestros expertos.
Contacta con el servicio de asistencia
Ponte en contacto con nuestro equipo de atención al cliente para recibir información, soporte técnico, asistencia para reclamaciones y mucho más.
¿Dónde comprar?
Encuentra fácilmente el distribuidor de Schneider Electric más cercano a tu ubicación.
Buscar preguntas frecuentes
Obtén las respuestas que necesitas examinando las preguntas frecuentes (FAQ) relacionadas con los temas.
Contacto con el servicio de ventas
Comienza tu consulta de ventas on-line y un experto se pondrá en contacto contigo.