Which phase current is used for the ANSI 49 (Thermal Overload) thermal replica calculation?

Issue

The thermal overload function is tripping, and the customer wants to verify which current value is used in the thermal model.

Product

MiCOM Series Protection relays

Environment

MiCOM protection relays
ANSI 49 Thermal Overload protection
Current measurement and thermal replica calculation

Cause

Clarification is required regarding how the relay determines the input current for the thermal overload function, especially during unbalanced load or fault conditions.

Resolution

The MiCOM relay family automatically uses the largest phase current among the three phases for the ANSI 49 thermal replica calculation. This ensures worst‑case heating is always considered in the thermal model.

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:

¿Necesitas ayuda?

¿Necesitas ayuda?

Selector de productos

Selector de productos

Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.

Pedir presupuesto

Pedir presupuesto

Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.

¿Dónde comprar?

¿Dónde comprar?

Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.

Centro de ayuda

Centro de ayuda

Encuentra recursos de soporte para todas tus necesidades en un solo lugar.

  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies