Is it possible to change application type of my Sepam?
Issue
A new protection application type is need for the existing Sepam.
Product Line
Sepam series 20
Sepam series 40
Sepam series 80
Environment
Application Type
Resolution
The answer is a little bit different according to the Sepam series:
- Sepam series 20 and 40: Modification of Sepam application type requires replacement of your complete Sepam. You need to order a new PowerLogic Protection Relay with the correct application type needed.
- Sepam series 60 and 80: As application type is in the cartridge, modification of Sepam application type requires only replacement of the cartridge. You need to order a new cartridge with the application type needed. Note: be careful, since you may need to purchase additional CCA63x CT adapters, depending on which Application Types are involved.
Note that in all cases, a firmware patch cannot modify application type of a Sepam.
Update Note (April 2026).
Publicado para: Schneider Electric España









