Formula to Calculate the Energy 64-bit INT in PM5000 Series

Issue
End user would like to obtain energy values via modbus register.


Product Line
PM5100, PM5110, PM5111, PM5310, PM5330, PM5331, PM5320, PM5340, PM5341, PM5560, PM5563

Environment
64-bit Energy Register

Cause
The energy values are stored in the INT64 bit format.

Resolution:

Formula to calculate the Energy for 64bit INT :
Energy = ( lower 32bit value )+( Higher 32bit value *232)
Energy = ( lower 32bit value )+( Higher 32bit value *4294967296)

Example to calculate the Active Energy Delivered (32 bit Formula)
Read register 3204 and 3206 in UINT32
Formula :
Higher 32 bit value = register value of 3206= 0
Lower 32 bit value= register value of 3204 = 89550842
( lower 32bit value )+( Higher 32bit value *4294967296)= Energy
(89550842)+(0*4294967296) = 89550.842 kWh

Example to calculate the Active Energy Delivered + Received (16 bit Formula)
Read register 3212 through 3215 as UINT16
Energy = ((register 4) * (2^48)) + ((register 3) * (2^32)) + ((register 2) *  (2^16)) + (register 1)
Formula:
Energy = ((Reg 3212) * (2^48)) + ((Reg 3213) * (2^32)) + ((Reg 3214) *  (2^16)) + (Reg 3215)

Note:
If the user is using Firmware version 1.3.7 then there is an option for Float 32-bit energy registers ( Registers 2700 onwards). The float 32 registers are the replication of the INT64 bit registers.
For more information reference kb FA204140

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies