Why is the subscription report saying successful when sent to the printer but nothing prints?

Issue

Unable to print subscription reports from PME/Web Applications/Reports even when PME indicates the print job was successful.
Reports print correctly only when first saved to the desktop.

Product Line

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment

Power Monitoring Expert
Printing Reports

Cause

The installed printer does not support printing subscription report PDFs generated by PME/Web Applications/Reports.

Resolution

To print subscription reports directly from PME, a TRUE PDF printer must be installed


The printer specifications needs to include PDF under the  Page Description Languages as shown below.

Page Description Languages (PDL)
PCL® 5c, PCL® 6, PDF direct, PostScript 3 compatible

Recommendation

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Support images

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies