{}

Nuestras marcas

Impact-Company-Logo-English Black-01-177x54

Web de Schneider Electric España

Bienvenido a nuestra web
¿Cómo podemos ayudarte?
Unable to access PowerChute Network Shutdown from OS default browser (FF31) on Oracle Linux 6.6 and Oracle Linux 6.7

Issue:
Install PCNS on Oracle Linux machine and try to access the web UI from OS default browser (Firefox 31.1.0)
The following error message appears:
Error: sec_error_ca_cert_invalid

Product Line:
PowerChute Network Shutdown  4.1

Environment:
OS: Oracle Linux 6.6 and Oracle Linux 6.7
Browser: Firefox 31.1.0 (Default Browser)
Build: PCNS 4.1

Cause:
The value of security.use_mozillapkix_verification is false.

Resolution:
1) Type "about:config" in browser’s address bar and hit Enter.
2) Navigate to "security.use_mozillapkix_verification" and toggle the value to "true".

About: Configuration

You will be able to access the web UI after doing this fix.

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango: