CM (Configuration Manager) Tool 2.0.0 - ION_Data archive is failing when historical data is selected

Issue:

When using Configuration Manager Tool 2.0.x, the Save to Archive process fails if Historical Data is included, resulting in a “Save to Archive was cancelled” message.

Image

Product Line:

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment:

Configuration Manager (CM) Tool 2.0.x

Cause:

This issue may occur due to one or more of the following conditions:

  • The SQL Server service account does not have sufficient write permissions on the selected archive output directory.
  • There is insufficient free disk space on the output drive to store the archive, including the ION_Data historical database.

When Historical Data is selected, the CM tool attempts to generate a database backup. If permissions or disk space are insufficient, the operation is canceled and no archive is created.

Resolution:

Warning
Take backups of any files before making changes. Ensure backups are stored in a safe location (for example, the Desktop).

Verify permissions and disk space

  1. Verify that the SQL Server service account has write access to the Configuration Manager archive output directory.
  2. Run the Configuration Manager Tool as Administrator.
  3. Confirm that the destination drive has sufficient free disk space to store the archive, including the ION_Data historical data.

If the issue persists after completing the checks above, the archive can be created manually using the workaround below.

Manual archive creation workaround

  1. Create the archive without selecting Historical Data.
  2. Unzip the generated archive to a known location.
  3. Open ComponentCollection.json (located in the root directory of the unzipped archive) using a text editor.
  4. Add the following JSON fragment:

{
"OperationType": 23,
"Processed": 1,
"Count": 1,
"Type": "Historical Data",
"ComponentItems": [
{
"Processed": true,
"Name": "ION_Data",
"DisplayName": "ION_Data",
"Attributes": [
{ "Name": "DatabaseName", "Value": "ION_Data" },
{ "Name": "Size", "Value": "316669952" },
{ "Name": "BackupSize", "Value": "227540992" },
{ "Name": "StartDate", "Value": "2015-11-19T16:00:00.0000000" },
{ "Name": "EndDate", "Value": "2016-06-22T03:45:00.0000000" }
]
}
]
}

5. Copy the ION_Data.bak database backup file into the following directory within the unzipped archive:

    • ...\Database_Backups

6. Re‑zip the archive, ensuring it includes:

    • The updated ComponentCollection.json
    • The ION_Data.bak file

7. Launch the Configuration Manager Tool and perform Load from Archive to confirm that the ION_Data metadata (start date, end date, etc.) is visible.

The metadata values do not need to exactly match the data range contained in the backup file.

Recommendation:

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

PME Versions

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:

¿Necesitas ayuda?

¿Necesitas ayuda?

Selector de productos

Selector de productos

Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.

Pedir presupuesto

Pedir presupuesto

Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.

¿Dónde comprar?

¿Dónde comprar?

Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.

Centro de ayuda

Centro de ayuda

Encuentra recursos de soporte para todas tus necesidades en un solo lugar.

  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies