What are the recommended overload current temporary or permanent, RM22JA21MR?
Short time overload for 3s
| Max Permissible Overload Current | |||
| Reference | E1-M | E2-M | E3-M |
| RM35JA31MW | 400mA for <3s | 1000mA for <3s | 2200mA for <3s |
| RM35JA32MW | 4A for <3s | 12A for <3s | 20A for <3s |
| RM22JA21MR | 900mA for <3s | 1400mA for <3s | 2000mA for <3s |
| RM22JA31MR | 900mA for <3s | 1400mA for <3s | 2000mA for <3s |
| RM35JA32MR | 4A for <3s | 12A for <3s | 20A for <3s |
| RM35JA32MT | 4A for <3s | 12A for <3s | 20A for <3s |
Continuous overload
| Max Permissible Continuous Overload Current | |||
| Reference | E1-M | E2-M | E3-M |
| RM35JA31MW | 360mA | 900mA | 2000mA |
| RM35JA32MW | 2A | 7.5A | 17A |
| RM22JA21MR | 800mA | 1200mA | 1600mA |
| RM22JA31MR | 800mA | 1200mA | 1600mA |
| RM35JA32MR | 2A | 7.5A | 17A |
| RM35JA32MT | 2A | 7.5A | 17A |