Cannot log in to FlexNet Publisher in PME 8.2

Issue
User cannot log in to the FlexNet Publisher web interface in Power Monitoring Expert (PME) 8.2 and receives a “Password is incorrect” message, even when using known credentials.

Product Line
Power Monitoring Expert 8.2

Note: Legacy article. This behavior applies to the FlexNet Publisher licensing implementation used in PME 8.2.

Environment
FlexNet Publisher (lmadmin)
Power Monitoring Expert licensing

Cause
In PME 8.2, FlexNet Publisher user credentials may not function as expected due to changes in license server configuration or credential initialization. The FlexNet Publisher web interface and administrator account still exist, but access can fail if the stored credentials are invalid or corrupted.

Resolution
Warning: This procedure involves editing configuration files. Always back up files before making changes.

Use the following steps to reset the FlexNet Publisher administrator password:

  1. Navigate to:
    C:\ProgramData\Schneider Electric\Floating License Manager\FLEXnet Publisher License Server Manager\conf
  2. Open the server.xml file in a text editor.
  3. Locate the administrator entry and update the password value, for example:
    id="admin" lastName="Administrator" password="(ENC-01)AxlKxBaCLbp4iPFsjJ6eOFtE+qoJWH8ThHIKN9DgdEgILS9j" passwordExpired="false"
  4. Save the file.
  5. Restart the lmadminschneider service.
  6. Open a browser and navigate to:
    http://<SERVERNAME>:8090
  7. Click Administration and log in using:
    Username: admin
    Password: admin

Recommendation

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Support Information

Schneider Electric España

Explorar más
Rango:
Explorar más
Rango:
  • Documentación de productos
  • Descargas de software
  • Selector de productos
  • Reemplazo de productos
  • Centro de ayuda y contacto
  • Encuentra nuestras oficinas
  • Pedir presupuesto
  • Dónde comprar
  • Closure of shop.se.com/es/es/ and shop.se.com/pro/es/es/
  • Schneider Electric Community
  • Carreras
  • Perfil corporativo
  • Denunciar una mala conducta
  • Accesibilidad
  • Sala de prensa
  • Inversores
  • EcoStruxure
  • Búsqueda de empleo
  • Blog
  • Política de privacidad
  • Aviso de Cookies
  • Condiciones de uso
  • Cambiar tu configuración de cookies