Intermittent Communications to EM4800 in PME
Issue
The EM4800's communications are intermittent, despite the device consistently responding to network pings.
Product Line
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment
EM4800
Cause
Network latency on the EM4800’s network segment is higher than expected. The default PME receive‑timeout value (10,000 ms) may be insufficient, causing intermittent communication drops.
Resolution
Increase the receive timeout for the EM4800 device:
- Open Management Console.
- Navigate to Devices and locate the EM4800.
- Right‑click the device and select Properties.
- In the Properties window, right‑click the white space and select Advanced Properties.
- Change Receive Timeout from 10,000 ms to 20,000 ms.
- Save and close.
Recommendation
If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com
Publicado para: Schneider Electric España
¿Necesitas ayuda?
Selector de productos
Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.
Pedir presupuesto
Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.
¿Dónde comprar?
Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.
Centro de ayuda
Encuentra recursos de soporte para todas tus necesidades en un solo lugar.