Issue
A report subscription with Active Directory Window Users as Recipients will fail when delivering the report
The subscription will fail with the following error in ION_SystemLog:
ION Web General ERROR 2020-05-21 19:31:31.877 Subscription Renderer Service SendSubscriptionNotification Server Name Exception sending notification for subscription '6'.
Microsoft.Practices.ServiceLocation.ActivationException: Activation error occured while trying to get instance of type LogWriter, key "" ---> Microsoft.Practices.Unity.ResolutionFailedException: Resolution of the dependency failed, type = "Microsoft.Practices.EnterpriseLibrary.Logging.LogWriter", name = "(none)". Exception occurred while: while resolving. Exception is: InvalidOperationException - The type LogWriter cannot be constructed. You must configure the container to supply this value. ----------------------------------------------- At the time of the exception, the container was: Resolving Microsoft.Practices.EnterpriseLibrary.Logging.LogWriter,(none) ---> System.InvalidOperationException: The type LogWriter cannot be constructed. You must configure the container to supply this value.
Environment
Power Monitoring Expert 2020
Report Subscription
Cause
There are two causes for this issue:
2) Missing config file XML that controls how to log this into SystemLog
Resolution
1) Update SubscriptionRenderer.exe.config
- Add the following section after the <configuration> tag (in the begging of the file)
<configSections>
<section name="loggingConfiguration" type="Microsoft.Practices.EnterpriseLibrary.Logging.Configuration.LoggingSettings, Microsoft.Practices.EnterpriseLibrary.Logging, Version=5.0.414.0, Culture=neutral, PublicKeyToken=31bf3856ad364e35" requirePermission="true" />
</configSections>
<loggingConfiguration configSource="diagnostic-log.config" />
It should like similar to this:
3) Restart IIS and ION Application Core service (that will force all the ION Application services to restart)
This will allow the report to be delivered by email for the windows users (active directory).
Additional Information
This may be addressed by the future release of a software cumulative update (CU2).
Publicado para: Schneider Electric España


¿Necesitas ayuda?
Empieza aquí
Encuentra respuestas ahora. Busca una solución por ti mismo, o ponte en contacto con uno de nuestros expertos.
Contacta con el servicio de asistencia
Ponte en contacto con nuestro equipo de atención al cliente para recibir información, soporte técnico, asistencia para reclamaciones y mucho más.
¿Dónde comprar?
Encuentra fácilmente el distribuidor de Schneider Electric más cercano a tu ubicación.
Buscar preguntas frecuentes
Obtén las respuestas que necesitas examinando las preguntas frecuentes (FAQ) relacionadas con los temas.
Contacto con el servicio de ventas
Comienza tu consulta de ventas on-line y un experto se pondrá en contacto contigo.