Clicking on the Settings link on the Power Monitoring Expert main page pops up an error window
Issue
When I use clicks on the "Settings" link on the Power Monitoring Expert main page a new error window pops up with link to GeneralSettingsDialog.html not found

Product
Power Monitoring Expert (PME) 8.1

Environment
Main web site is using non default address like /PQweb instead of the default /web

Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).*

1) Navigate to [PME install]\Applications\ApplicationFramework\content
2) Backup the file GeneralSettingsDialog.js
3) Edit the original file with a text editor
Replace the line TemplateUtil.LocAndLoad('/Web/Content/GeneralSettingsDialog.html', with the correct with the setup URL
For example
TemplateUtil.LocAndLoad('/PQWeb/Content/GeneralSettingsDialog.html',
4) Close all web clients an restart IIS
5) Verify that the link now open the settings page.

Schneider Electric Suomi

Lue lisää
Tuotesarja:
Lue lisää
Tuotesarja:
  • Tuotedokumentaatio
  • Ohjelmistolataukset
  • Tuotevalitsin
  • Tuotteen korvaaminen ja vaihtaminen
  • Asiakaspalvelukeskus
  • Etsi toimistomme
  • Pyydä tarjous
  • Osta täältä
  • Shop.se.com/fi/fi sulkeutuu
  • Schneider Electricin yhteisö
  • Uramahdollisuudet
  • Yritys
  • Ilmoita väärinkäytöksestä
  • Saavutettavuus
  • Newsroom
  • Sijoittajat
  • Tutustu EcoStruxure
  • Toimipisteet Suomessa
  • Löydä jälleenmyyjä
  • Avoimet työpaikat
  • Blogi
  • Tietosuojakäytäntö
  • Evästeilmoitus
  • Käyttöehdot
  • Muokkaa evästeasetuksia