How to save the parameters in the keypad and upload to another identical ATV630 drive.

Article available in these languages: Hollanti

Issue:
Trying to save the parameters in the keypad and upload them to another identical ATV630 drive.

Product Line:
ATV630 drives

Environment:
Keypad

Cause:
Transferring files

Resolution:
Go to Main menu and scroll down to menu 7: File Management and press Ok.
Select 7.1-Transfer config file- select copy from the drive ( to save to the keypad) or select Copy to the drive (to upload the keypad setting to the drive).