What are remedies for the Supply Mains Overvoltage Fault (OSF) on the Altivar Process Drive?

Issue:
Supply Mains Overvoltage Fault (OSF) on the Altivar Process Drive

Product Line:
Altivar Process Drives (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar 600 and 900 Process Drive

Cause:
N/A

Resolution:
This fault appears when the nominal voltage exceeds the maximum value of the drive

Possible Remedies:
  • Check Supply Line Voltage
    • Check for Power Factor Correction Capacitors
  • Measure DC Bus Voltage (PA+ and PC-) On an ATV630 these terminals are located behind a black sticker
    • Check for any additional or DC generating device next to the drive
  • If there is an IT system, (High Leg Delta or Corner Grounded), suggest to disconnect the EMI filter and then power cycle the drive and see if the fault returns..
    • Measure each incoming phase to ground to be sure whether you have a high leg. If so, that high leg could be overcharging the EMI filter capacitors, and in turn, overcharging the DC bus


Schneider Electric Suomi

Lue lisää
Tuotesarja:
Lue lisää
Tuotesarja:
  • Tuotedokumentaatio
  • Ohjelmistolataukset
  • Tuotevalitsin
  • Tuotteen korvaaminen ja vaihtaminen
  • Asiakaspalvelukeskus
  • Etsi toimistomme
  • Pyydä tarjous
  • Osta täältä
  • Shop.se.com/fi/fi sulkeutuu
  • Schneider Electricin yhteisö
  • Uramahdollisuudet
  • Yritys
  • Ilmoita väärinkäytöksestä
  • Saavutettavuus
  • Newsroom
  • Sijoittajat
  • Tutustu EcoStruxure
  • Toimipisteet Suomessa
  • Löydä jälleenmyyjä
  • Avoimet työpaikat
  • Blogi
  • Tietosuojakäytäntö
  • Evästeilmoitus
  • Käyttöehdot
  • Muokkaa evästeasetuksia