{}

Tuotemerkkimme

Impact-Company-Logo-English Black-01-177x54

Tervetuloa Schneider Electricin verkkosivustolle

Tervetuloa sivustollemme.
Hae usein kysyttyjä kysymyksiä
What does an EEF1 fault on an Altivar Process Drive mean?

Article available in these languages: Espanja

Issue:
Troubleshoot for an EEF1 fault on a Process Drive

Product Line:
Altivar 6xx and 9xx Process Drives

Environment:
All

Cause:
An error of the internal memory of the control block has been detected.

Resolution:
Verify the environment (electromagnetic compatibility).
This detected error requires a power reset. Remove line voltage until the display goes all the way out. Then reapply line voltage.
If cycling line voltage doesn't clear the fault, save your programming in the keypad or SoMove, and perform a factory reset.
After factory reset cycle line voltage again.
If the fault remains, drive replacement is required.

Schneider Electric Suomi

Lue lisää
Tuotesarja:
Artikkelit, joista voi olla apua
Lue lisää
Tuotesarja: