Is any action needed before updating M580 Firmware to version 4.01 or later?

Updating from firmware version 3.20 or earlier to firmware version 4.01 or later must be done following a two-steps specific procedure. For instructions, refer to the M580 Firmware Installation Guide.

Besides, thanks for following the next recommendations if intended to upgrade the M580 controller with a firmware version 4.01 or later, as explained in Firmware History Release Notes RN0000000110.03 :

  1. In case you are using a Modicon M580 RTU module in association, first upgrade the RTU module to firmware version 03.02.02 or later and test your application.
  2. In case you are using a Modicon BMENOC0301 or BMENOC0311 module in association, first upgrade the BMENOC module to firmware version 02.20 or later and test your application.
  3. In case you are using a Modicon BMENOC0321 module in association, first upgrade the BMENOC module to firmware version 1.09 or later and test your application.

Schneider Electric France

  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Contacter notre équipe support pour les particuliers
  • Trouver des sites Schneider Electric
  • Contacter notre équipe commerciale pour une affaire
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Accessibilité
  • Salle de presse
  • Relations Investisseurs
  • Plan du site
  • mySchneider
  • Parcourir les FAQs
  • EcoStruxure
  • Blog
  • Mentions legales
  • Conditions d'utilisation
  • Protection des données
  • Mention sur les cookies
  • Conditions Générales de Vente
  • Modifier vos paramètres de cookies