Issue
Symmetra PX UPS shows power module status as "NA" within the Network Management Card interface when the module is first installed
Product Line
- Symmetra PX
- UPS Network Management Card 1 (NMC1) - AP9617, AP9618, AP9619
- UPS Network Management Card 2 (NMC2) - AP9630/30CH, AP9631/31CH
Environment
- All UPS firmware revisions
- All NMC1 and NMC2 firmware revisions
Cause
Still under investigation
Resolution
Perform a reboot on the NMC management interface. In order to do this, access the web interface and navigate to the Administration tab->General->Reset/Reboot and select "Reboot management interface." Press apply.
If caller is at the UPS they can also press and release the pin hole reset button to accomplish the same reset.
Released for: Schneider Electric Hong Kong