Can a remote speed signal be wired to an ATV212 S-Flex drive?
Issue:
Remote speed signal wiring on an ATV212 S-Flex drive
Product Line:
Altivar ATV212, SFlex 212
Environment:
All
Cause:
Customer didn't know how the speed signal was wired in the ATV212 S-Flex.
Resolution:
Yes, a 0-10Vdc, 0-20mA, or a 4-20mA analog signal can be wired to the VIA Terminal on the drive.
Only a 0-10v or PTC motor thermal probe can be used with terminal VIB.
NOTE: Dipswitches are used to set these terminals for Voltage, Current or PTC.
Remote speed signal wiring on an ATV212 S-Flex drive
Product Line:
Altivar ATV212, SFlex 212
Environment:
All
Cause:
Customer didn't know how the speed signal was wired in the ATV212 S-Flex.
Resolution:
Yes, a 0-10Vdc, 0-20mA, or a 4-20mA analog signal can be wired to the VIA Terminal on the drive.
Only a 0-10v or PTC motor thermal probe can be used with terminal VIB.
NOTE: Dipswitches are used to set these terminals for Voltage, Current or PTC.