Issue:
After upgrading system Java PowerChute Network Shutdown web interface is not accessible.
Product:
PowerChute Network Shutdown versions v3.x, v4.0, v4.1, v4.2
Environment:
All supported OS
Cause:
When upgrading Java in most cases the older version in uninstalled so the path PowerChute uses to access Java no longer exist.
Solution:
Run the PowerChute installer which will discover the new path.
NOTE: This issue is resolved in PowerChute Network Shutdown v4.3+ which supports OpenJDK.
After upgrading system Java PowerChute Network Shutdown web interface is not accessible.
Product:
PowerChute Network Shutdown versions v3.x, v4.0, v4.1, v4.2
Environment:
All supported OS
Cause:
When upgrading Java in most cases the older version in uninstalled so the path PowerChute uses to access Java no longer exist.
Solution:
Run the PowerChute installer which will discover the new path.
NOTE: This issue is resolved in PowerChute Network Shutdown v4.3+ which supports OpenJDK.