Welcome to the Schneider Electric Website

Welcome to our website.

Select your location

Welcome the the Schneider Electric French website. It looks like you are located in the United States, would you like to change your location?

Traduisez en francais
View all   ComPact NS
33320 Product picture Schneider Electric

33320

Green premium brand logo
33320 Product picture Schneider Electric
33320
Green premium brand logo

circuit breaker Compact NS630bN - 630 A - 3 poles - drawout - without trip unit

Show more characteristics
  • 3,652.00 HKD
The maximum number of products that can be compared is 4. Remove already added products.

  • Main
    range
    ComPact
    range of product
    ComPact NS630b...1600
    device short name
    Compact NS630bN
    product or component type
    Basic frame
    device application
    Distribution
    Number of poles
    3P
    [In] rated current
    630 A at 50 °C
    [Ue] rated operational voltage
    690 V AC 50/60 Hz
    network type
    AC
    network frequency
    50/60 Hz
    suitability for isolation
    Yes conforming to EN/IEC 60947-2
    utilisation category
    Category B
    [Icu] rated ultimate short-circuit breaking capacity
    30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
    Performance level
    N 50 kA 415 V AC
    control type
    Toggle
    Rotary handle
    mounting mode
    Drawout
    Complementary
    [Ui] rated insulation voltage
    800 V AC 50/60 Hz conforming to IEC 60947-2
    [Uimp] rated impulse withstand voltage
    8 kV conforming to IEC 60947-2
    [Ics] rated service short-circuit breaking capacity
    30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
    40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
    50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
    50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
    50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
    [Icw] rated short-time withstand current
    19.2 kA 1 s conforming to IEC 60947-2
    integral instant protection
    40 kA
    mechanical durability
    10000 cycles conforming to IEC 60947-2
    electrical durability
    2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
    4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
    5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
    6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
    power losses
    19 W
    mounting support
    Backplate
    connection pitch
    70 mm
    protection type
    Without protection
    Height (H)
    327 mm
    Width (W)
    210 mm
    Depth (D)
    147 mm
    Environment
    standards
    IEC 60947-2
    product certifi