circuit breaker Masterpact NW50H2 - 5000 A - 3 poles - fixed - w/o trip unit

Show more characteristics
  • 211,464.00 HKD
The maximum number of products that can be compared is 4. Remove already added products.

  • Main
    range of product
    Masterpact NW
    product or component type
    Basic frame
    device short name
    Masterpact NW50
    circuit breaker name
    Masterpact NW50H2
    poles description
    3P
    network type
    AC
    breaking capacity code
    H2
    suitability for isolation
    Yes conforming to IEC 60947-2
    utilisation category
    Category B
    Complementary
    network frequency
    50/60 Hz
    control type
    Push-button
    mounting mode
    Fixed
    [In] rated current
    5000 A at 40 °C
    [Ui] rated insulation voltage
    1000 V AC 50/60 Hz conforming to IEC 60947-2
    [Uimp] rated impulse withstand voltage
    12 kV conforming to IEC 60947-2
    [Icm] rated short-circuit making capacity
    220 kA 690 V AC at 50/60 Hz
    286 kA 525 V AC at 50/60 Hz
    [Ue] rated operational voltage
    690 V AC 50/60 Hz conforming to IEC 60947-2
    circuit breaker CT rating
    5000 A
    breaking capacity
    150 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
    150 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
    100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
    130 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
    150 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    [Ics] rated service breaking capacity
    100 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
    130 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
    protection type
    Without protection
    mechanical durability
    10000 cycles with maintenance conforming to IEC 60947-2
    5000 cycles without maintenance conforming to IEC 60947-2
    electrical durability
    AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
    1500 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
    1500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
    AC-23A: 1500 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
    AC-23A: 1500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
    connection pitch
    230 mm
    [Icw] rated short-time withstand current
    100 kA 1 s conforming to IEC 60947-2
    100 kA 3 s conforming to IEC 60947-2
    integral instant protection
    243…297 kA
    maximum breaking time
    25 ms
    maximum closing response time
    80 ms
    height
    352 mm
    width
    767 mm
    depth
    297 mm