{}

Márkánk

Impact-Company-Logo-English Black-01-177x54

Üdvözöljük a Schneider Electric weboldalán!

Üdvözöljük weboldalunkon!
GYIK keresése
Which service bypass panel should be used for single phase Symmetra UPS systems?

Issue

There are many single phase service bypass panels; which one should I use with my single phase Symmetra UPS?


Product Line

Symmetra Power Array
Symmetra RM
Symmetra LX
Single Phase Service Bypass Panels


Environment

All serial ranges


Cause

Due to their design, different UPS systems require different service bypass panels.


Resolution

This table provides a reference as to which service bypass panel must be used for a single phase Symmetra system.

Bypass PanelUPS SystemsRelay TypeBypass InputUPS InputUPS OutputPDU Panel
SBP6KRMT2USymmetra 6k RM 200/208/240Make-before-breakL6-30P, HardwireL6-30R, HardwireL6-30P, Hardwire(1) L6-20, (2) L6-30
SBP6KRMI2USymmetra 6k RM 220/230/240Make-before-breakHardwireHardwireHardwire(4) C19
SBP16KTSymmetra Power Array: 208 InputBreak-before-makeHardwireHardwireHardwireHardwire
SBP16KPSymmetra LX 200, 208, 240V; Power Array 240 Input; 12k RM 200, 208, 240VMake-before-breakHardwireHardwireHardwireHardwire
SBP16KRMI4USymmetra LX 200-240V;12k RM 200-240Make-before-breakHardwireHardwireHardwire(3) 30A Hardwire
SBP16KRMP4USymmetra LX 200/208/240Make-before-breakHardwireHardwireHardwire(4) L14-30
SBP20KPSmart-UPS RT 20KMake-before-breakHardwireHardwireHardwireHardwire

Schneider Electric Hungary

Tudjon meg még többet
Tartomány:
Hasznos cikkek
Tudjon meg még többet
Tartomány: