In the 30072-450-61 Manual for the ATS48 on page 76, it shows contacts for ``KM1`` & ``KM2``. What are they?

Issue:
What are the the contacts labelled KM1 and KM2 feeding into the IC1 forward contactor and IC2 reverse contactor?

Product line:
Altistart 48, ATS48

Environment:
All enclosed

Cause:
Typo error in the instruction bulletin

Resolution:
This is an error in the manual. KM1 should be labelled IC1 and KM2 should be labelled IC2.
These are auxiliary contacts from the forward and reverse isolation contactors, used for electrical interlocking. This helps prevent closure of both contactors at the same time.

Schneider Electric Indonesia

Jelajahi lebih lanjut
Rentang:
Jelajahi lebih lanjut
Rentang:

Perlu bantuan?

Perlu bantuan?

Pemilih produk

Pemilih produk

Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.

Dapatkan Penawaran Harga

Dapatkan Penawaran Harga

Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.

Tempat pembelian

Tempat pembelian

Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.

Pusat Bantuan

Pusat Bantuan

Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.

  • Dokumentasi Produk
  • Unduhan Perangkat Lunak
  • Pemilih Produk
  • Penggantian dan Penggantian Produk
  • Pusat Bantuan dan Kontak
  • Temukan Kantor kami
  • Dapatkan penawaran harga
  • Tempat Pembelian
  • Komunitas Schneider Electric
  • Karier
  • Profil Perusahaan
  • Melaporkan pelanggaran
  • Aksesibilitas
  • Newsroom
  • Investor
  • EcoStruxure
  • Pencarian Pekerjaan
  • Blog
  • Kebijakan Privasi
  • Pemberitahuan Cookie
  • Ketentuan penggunaan
  • Change your cookie settings