User has added a new PM8000 or PM5500 device to Management Console and the devices are communicating and providing real time data. When selecting the "Update OPC" in Management Console, no new devices are added to OPC tags.
Product
Power Monitoring Expert (PME) 8.0, 8.1
Environment
DefaultMeasurements.xml is located in [PME install]\config\IONServices
Cause
PME 8.0 uses a folder called DefaultMeasurementsExt to add device types without having to add to devices to DefaultMeasurements.xml. When the Update OPC is selected in Management Console, PME will look for the DefaultMeasurements.xml in the config folder first. If DefaultMeasurements.xml is found, PME will look for the DefaultMeasurementsExt folder in the same location.
Resolution
One work around is to copy the folder DefaultMeasurmentsExt from the ...\system\IONServices\ to ...\config\IONServices.
A better option would be to transfer the custom content of the DefaultMeasurement.xml file to new extension files in the ...\system\IONService\DefaultMeasurementsExt folder, then remove the DefaultMeasurements.xml file from the config folder.
See FA327559 for information on how to create an extension file
Diterbitkan untuk: Schneider Electric Indonesia
Perlu bantuan?
Mulai di sini!
Temukan jawaban sekarang. Cari solusi sendiri, atau hubungi salah satu pakar kami.
Hubungi Dukungan
Hubungi tim layanan pelanggan kami untuk mendapatkan informasi lebih lanjut, bantuan teknis, penanganan keluhan, dan lainnya.
Tempat pembelian
Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.
Jelajahi FAQ
Dapatkan jawaban yang Anda butuhkan dengan menelusuri Pertanyaan yang Sering Diajukan (FAQ) berdasarkan topik.
Hubungi Bagian Penjualan
Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.