Altivar Process Drives - What are the password requirements when changing the Webserver password?

Issue:
What is required when changing the webserver password?

Product line:
Altivar 6xx and 9xx Process Drives

Environment:
All version V1.5 or greater

Cause:
Customer wants to change the factory issued password

Resolution:
Starting with V1.5 or greater, Admin/Admin is not the default login/password.  Each password is unique to the specific drive.

The new password must be:

  • A total of eight characters
  • At least one upper-case letter
  • At least one lower-case letter
  • At least one special character (for example, @, #, $)
  • No blank characters
NOTE: After five unsuccessful login attempts, the access must be reactivated by the administrator.

Schneider Electric recommends to:
  • Modify the password every 90 days
  • Use a dedicated password (not related to your personal password)

NOTE: No responsibility is assumed by Schneider Electric for any consequences if anyone hacks your
product password and if you use the same password for personal usage.