{"support":{"yesButton":"Ya","noButton":"Tidak","feedback":{"title":"Apa yang dapat kami lakukan untuk menjadi lebih baik?"},"submitButton":"Kirim","successMessage":"Terima kasih atas umpan balik Anda","title":"Apakah ini bermanfaat?","feedbackPercentLabel":"orang merasa bahwa ini bermanfaat","captcha":{"error":"Silakan centang kotak"}}}
FAQ Pencarian

What is the condition for Phase Loss Fault in EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)

Phase loss fault comes into play in EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420) when max imbalance is more than 85% among 3 phase current.

Where,Imbalance factor (%) = (Imax phase - Imin_phase) / Imax_phase x 100%