{"support":{"yesButton":"Ya","noButton":"Tidak","feedback":{"title":"Apa yang dapat kami lakukan untuk menjadi lebih baik?"},"submitButton":"Kirim","successMessage":"Terima kasih atas umpan balik Anda","title":"Apakah ini bermanfaat?","feedbackPercentLabel":"orang merasa bahwa ini bermanfaat","captcha":{"error":"Silakan centang kotak"}}}
FAQ Pencarian

What can cause a Load Slipping Fault (AnF) on a ATV320 drive?

Issue:
Cause of a Load Slipping Fault (AnF) on a ATV320 drive.

Product Line:
 ATV320 drive

Environment:
 AnF faults

Cause:
 The difference between the output frequency and the speed feedback is not correct.

Resolution:
Check the motor, gain and stability parameters.
Check the size of the motor /drive load.
Check the encoder’s mechanical coupling and its wiring.
Recheck all the motor parameters
May need to add a braking resistor and turn off the brA.